FLAME SENSOR
|
Product name | Flame sensor |
---|---|
Model | FS-2000E |
Detection area | Distance: 33ft.(10m) [2.75" (7cm) lighter flame, in front ] Angle: Approx. 120°conically Adjustment range: Horizontal 25° … by base unit Vertical 30° (4 steps) … by sensor head |
Sensitivity adjustment | Detection timer 4 steps (0.2 sec., 1 sec., 6 sec and 30 sec.) |
Power supply | 10V to 30VDC (non-polarity) |
Power consumption | Stand by : 25mA or less Alarm : 75mA or less (alarm sound ON) 40mA or less (alarm sound OFF) |
Alarm output | Dry contact relay Form C (alarm : open / close) Contact action : off-delay (approx. 2 sec.) Contact capacity : 30V(AC/DC)0.3A, protective esistance 3.3 ohms |
Alarm memory | Auto-reset operation (on/off setting available) Memory LED blinks for 3 min. then lights on for 47 mi n |
LED | Alarm LED (red) : light on for off-delay 10 sec. Memory LED (yellow) : light on when memory indicated, blink when power turned on |
Alarm sound (buzeer) | Alarm : Sounds intermittently every 0.2 sec. during off-delay 10 sec. Volume : 80dB or more at 3.3ft (1m) ahead (silent setting is available) |
Temper output | Dry contact relay Form B (N.C.) Action : open when cover is detached Capacity : 30V (AC/DC) 0.1A |
Wiring | Terminals |
Ambient temp. range | +14F to +140F (-10C to +60C) without condensation and freeze |
Installation | Indoor (ceiling or wall mount) |
Weight | Approx. 5.3oz (150g) |
Appearance | ABS resin (white) |
Accessories | Tapping screw Φ4×25.2pcs. Sensor locking screw Φ3×6.1pce. |
Optional | Celling mount attachment [BCW-401] |